220V Online UPS – Uninterrupted Power Supply MAXX – 220V For Marine


Ref: IMPA Code – 

Capacity Available – 1000VA/600W, 1500VA/900W, 2000VA/1200W & 3000VA/1800W

Compact size

Easy to install and operate

Cold start function

Modem/LAN internet protection

AVR boost and buck

Compare

Features:

  • High power density
  • Online double conversion with full digital control
  • Wide input voltage range: 110~300Vac
  • High input power factor of 0.99 with Power Factor Correction (PFC)
  • Selectable output voltages: 208V, 220V, 230V, and 240V
  • Smart charger design for enhanced battery performance
  • Maximum charging current of 12A for extended runtime units
  • Emergency power off (EPO) function
  • Eco mode for energy savings
  • Generator compatibility
  • Cold start capability
  • Intelligent fan speed control
  • User-friendly LCD interface
  • VMultiple communication interface: RS232 (USB/EPO/Relay card /SNMP card optional)
  • Multiple protection functions: short-circuit, overload, overheat, battery overcharge and over-discharge, output low voltage and fan fault alarm

 

SKU: 5487FB8/22-2-1-1-1-1-2-3-1-1-2-1-2-1-2-1-1-1-2-1-1-2-1-1-2-1-2-2-1 Categories: ,
Brands

MAXX

Technical Specifications

MODEL MAXX-UPS10 ONK220 MAXX-UPS20 ONK220 MAXX-UPS30 ONK220
Capacity 1000VA/900W 2000VA/1800W 3000VA/2700W
INPUT
Nominal voltage 208/220/230/240Vac
Input voltage range 110~300Vac (176~264Vac @ 100% load)
Power factor ≥0.99
FREQUENCY
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
OUTPUT
Output voltage 208/220/230/240Vac
Voltage regulation ±1%
Power factor 0.9
Output Frequency Line mode 46~54Hz or 56~64Hz
Bat. mode (50/60±0.1%)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤3% Linear load
≤5% Non linear load
Transfer time AC mode to Bat. mode 0 ms
Inverter to Bypass 4 ms (Typical)
Output waveform Pure Sinewave
EFFICIENCY
AC mode 88% 90% 91%
Battery mode 85% 87% 88%
BATTERY
Battery Number 3—6 4—6 6—8
Capacity (Standard unit) 9Ah/12V (7Ah/12V optional)
Typical recharging time 4 hours (To 90% of full capacity)
Charging voltage 41.1Vdc±1%

82.2Vdc±1%

54.8Vdc±1%

82.2Vdc±1%

82.2Vdc±1%

109.6Vdc±1%

Charging current (Max.) 1A 1A 1A
INDICATORS
LCD Input voltage, Input frequency, Output voltage, Output frequency, Load percentage,
Battery voltage, Inner temperature& Remaining battery backup time
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continuously beeping
PHYSICAL
Dimension W×D×H 144×399

×209mm

191×460×337mm
Net weight 12.5kg 24.5kg 29.5kg
ENVIRONMENT
Operating temperature 0℃~40℃
Storage temperature -25℃~55℃
Humidity range 20~95%RH @ 0~40℃ (Non condensing)
Altitude <1500m, derating required when>1500m
Noise level <50dB at 1 Meter
STANDARDS
Safety IEC/EN 62040-1, IEC/EN 62477-1
EMC IEC/EN 62040-2 (IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11, IEC 61000-2-2)