110V Online Rack Type UPS – Uninterrupted Power Supply MAXX – 110V For Marine


Ref: IMPA Code – 

Capacity Available – 1000VA/600W, 1500VA/900W, 2000VA/1200W & 3000VA/1800W

Compact size

Easy to install and operate

Cold start function

Modem/LAN internet protection

AVR boost and buck

Compare

Features:

  • Rack/Tower convertible design
  • Online double conversion with full digital control
  • Wide input voltage range: 110~300Vac
  • High input power factor of 0.99 with Power Factor Correction (PFC)
  • Selectable output voltages: 208V, 220V, 230V, and 240V
  • Smart charger design for enhanced battery performance
  • Maximum charging current of 12A for extended runtime units
  • Emergency power off (EPO) function
  • Eco mode for energy savings
  • Generator compatibility
  • Hot-Swappable battery design
  • Cold start capability
  • Intelligent fan speed control
  • User-friendly LCD interface
  • VMultiple communication interface: RS232 (USB/EPO/Relay card /SNMP card optional)
  • Multiple protection functions: short-circuit, overload, overheat, battery overcharge and over-discharge, output low voltage and fan fault alarm

 

SKU: 5487FB8/22-2-1-1-1-1-2-3-1-1-2-1-2-1-2-1-1-1-2-1-1-2-1-1-2-1-2-2-1-1 Categories: ,
Brands

MAXX

Technical Specifications

MODEL MAXX-UPS10 ONK 110 MAXX-UPS15 ONK 110 MAXX-UPS20 ONK 110 MAXX-UPS30 ONK 110
Capacity 1000VA/1000W 1500VA/1350W 2000VA/1800W 3000VA/2700W
INPUT
Nominal voltage 100/110/115/120/125Vac
Input voltage range 55~150Vac (90~150Vac @ 100% load)
Power factor >0.99 (Full load)
Input connection NEMA 5-15P NEMA 5-20P NEMA L5-30P
Cord length 1.8m
FREQUENCY
Frequency range 40~70Hz (50/60Hz Auto-Sensing)
OUTPUT
Output voltage 100/110/115/120/125Vac
Voltage regulation ±1%
Power factor 1 0.9
Output Line mode 46~54Hz/56~64Hz, synchronize with input
Frequency Batt. mode 50/60±0.1Hz
Crest factor 3:01
Harmonic distortion (THDv) 2% Linear load
5% Non-linear load
Transfer time AC mode to Batt. mode 0 ms
Inverter to Bypass 4 ms (Typical)
Output waveform Pure Sinewave
Output receptacles Programmable (Optional) 5-15R×4 5-20R×4 5-20R×3
Non-programmable L5-20R×1 (Optional) + 5-20R×4 L5-30R×1+5-20R×3
EFFICIENCY
AC mode 91% 92%
ECO mode 95% 96% 96.50%
BATTERY
Battery Number 3 4 6 6
Battery capacity 9Ah/12V
Typical recharging time 4 hours (To 90% of full capacity)
Charging voltage 41.1Vdc±1% 54.8Vd c±1% 82.2Vdc±1%
Charging current (Max.) 2A
INDICATORS
LED / LCD Display Line mode, Bat. mode, ECO mode, Bypass mode, Battery low voltage, Overload & UPS fault
ALARM
Battery mode Beeping every 4 seconds
Battery low Beeping every second
Overload Beeping twice every second
Fault Continuously beeping
PHYSICAL
Dimension W×D×H 440×460×86.5mm 440×500×86.5mm 440×500×86.5mm 40×640×86.5mm
Net weight 17.2kg 20.2kg 21.3kg 28.7kg
ENVIRONMENT
Operating temperature 0~40 ºC
Humidity range 0~95% (Non – condensing)
Altitude 0~3000 (1000~3000 derating required)
Noise level ≤45dB ≤45dB ≤45dB ≤50dB
STANDARDS
Safety UL1778 5th Edition CSA C22.2 NO.107.3-14
FCC FCC Part 15, Subpart B, ClassA ANSI C63.4-2014